Header
Home | Sitemap  
Sections
Syndication



Voltage Conversion Strategy

by

image

 

Voltage Conversion Strategy

For minimum power consumption, it is important for the system designer to understand the voltage and current needs of the load. Typically, some portion of the power overhead (i.e., power consumed by the converter from the source but not delivered to the load) of the converter is fixed, regardless of power delivered to the load, and some portion is variable, and is directly proportional (to a first approximation) to the power delivered to the load at any given time. The fixed portion of the overhead in most designs is commensurate with the maximum current capability of the converter. Operating a converter significantly below its maximum design value, therefore, represents a waste of power because the same output power could be delivered by a converter with a lower maximum power output capability and, therefore, lower fixed overhead. Importantly, as the power consumed by the load falls, the efficiency of the total system drops, because a greater fraction of total consumed power is consumed by the converter, instead of the load. Reducing the power consumption of the load becomes an effort with diminishing returns, for, although the absolute value of load power saved is directly reflected in a reduction in input power, the percentage improvement in input power becomes less and less as the load power becomes comparable with the converter overhead. In the limit, the minimum power the system can consume is that of the converter itself. This means, for example, that no matter how low-power the standby circuits (e.g., oscillators, timers) are in a battery-powered network node, the maximum lifetime of the node ultimately is determined by the overhead of its power converter. It is for this reason that it is desirable to avoid the use of power converters completely, by matching the current and voltage requirements of the load with those available from the source. When this is done, one gets the full benefit one expects from a reduction in load power consumption; a 40 percent power reduction of the load (achieved, say, by shrinking the size of the circuits in a smaller-geometry IC process), results in a 40 percent reduction in power consumed from the source and a 40 percent increase in battery life.

Should the use of a converter be necessary, however, a method to ameliorate its fixed overhead power consumption is to operate it in "burst mode" (i.e., cycling it on and off). When the converter is off, the load is supplied from the filter capacitor, the value of which usually is made as large as possible to extend the "off" periods. When the output voltage reaches a low threshold, the converter is restarted, increasing the voltage until an upper threshold is reached, when the converter is turned off again. Use of burst mode can be considered either a method of regulation (especially if no other form of regulation is present), or a strategy for power reduction (especially if a second type of regulation is present when the converter is active). It is especially useful for lightly loaded converters, which may otherwise operate very inefficiently due to their relatively large power overhead, and for loads (such as standard cell digital logic) that are insensitive to relatively large variations in their supply voltage. Burst mode is often employed during the sleep periods of wireless snesor network communication protocols, during which the converter load may consist of a single clock oscillator and counter, used to count down the time until the next active period.

The power consumption of wireless sensor network nodes typically varies significantly over time; it is very low while the node is asleep, rises several orders of magnitude for a brief period of transmission and/or reception, then returns to its low value as the node returns to sleep. For example, a node may have a constant 30-μA current drain while asleep, but have an additional 400-μs-long pulse of 20 mA every 2 seconds when the receiver is active. Supplying this load at all times from a single converter, capable of handling the maximum power sunk by the load at all times, would imply that for the vast majority of time, the converter was operating in a very inefficient mode; a converter capable of sourcing 20 mA may have a fixed overhead current of 20 μA. The average current drain of such a system would be

A much more efficient system would be to employ two converters — a first converter (perhaps an inductive switching converter) providing power only when the node is active, followed by a second converter (perhaps an integratable capacitive switching converter) providing power during sleep mode. The first converter could be the ssme one used in the first design, and would be optimized to supply the 20-mA active current. The second converter would be designed for optimum efficiency supplying standby current drain values (e.g., an overhead of 3 μA while supplying 30 μA). The average current drain of this design is

The second design has reduced the average power consumption of the system by 31 percent.

The design of such multiple-converter systems results in additional system complexity; for example, the switching of the converters must not produce any momentary spikes or glitches in the supply, and the warm-up behavior of the second converter must be well-characterized so that it can be ready to supply the load of the active network node when required. A multiconverter design can be significantly more efficient than the single-converter approach, however, and can greatly extend the battery life of a network node. Burst mode may also be used in some applications to create a low-output mode from a high-output converter, with reasonably good efficiency, and thereby get the performance of two converters with only one set of components.

This quirk of converter behavior also must be considered in the design of application-flexible wireless sensor network nodes. When designing the power converter system for a network node for which the end application, and, therefore, the sensors and actuators that may be used, is not known, it is tempting to place a single power converter in the design, capable of handling the worst-case envisioned power consumption by the load. Unfortunately, this saddles the typical application with less-than-optimum overall power consumption. One solution to this problem is to offer multiple converters to supply the node transducers and ask the user (or OEM supplier) to select the proper one. This solution is expensive, due to the duplication of converters and their associated die and board area, chip pin-outs, and external components. A more economically attractive solution is to design a single, programmable converter, the maximum power capability of which may be adjusted via an external port. The use of such a converter is not a panacea, however; its design is nontrivial, and often only a limited range of power capabilities is possible without changing external components.

The problem of matching power converter efficiency with a time-varying load affects all supplied circuits. To optimize system power consumption, the network node designer must understand not just the maximum current required by all loads, but how each load's current requirements vary with time. The analysis of each load's current requirements can become complex, especially when multiple independent loads are driven from the same converter (e.g., an LCD driver and standby timing circuits), or when the outputs of multiple converters are associated (e.g., an LCD driver and its backlight). A thorough analysis that covers all potential states of operation should be performed to ensure that no case is overlooked and that the transitions between states are well understood.

In addition to these factors, the required temperature coefficient of the converter output must also be considered in a low-power design. For example, a wireless sensor network node may be required to operate over the industrial temperature range of -20°C to +85°C. A CMOS digital circuit in the network node may meet its speed requirements with a 1.0 V supply at a temperature of –20°C, but require a 1.2-V supply to achieve the same speed at +85°C. A converter with a temperature coefficient of zero ppm/C that supplies this circuit would require an output voltage of 1.2 V to ensure operation over the entire operating temperature range. This represents a waste of power over most of the temperature range, when a lower supply voltage would be sufficient. A better design uses a converter with a positive temperature coefficient that matches that of the load; such a converter would produce 1.2 V at +85°C, but a lesser voltage at lower temperatures, reducing the average power consumed by the system. Other loads, such as liquid crystal displays, can require a supply with a negative temperature coefficient. Matching the temperature coefficient of supplies with the needs of loads is important to minimize system power consumption, but this can be a complex task when multiple loads are present. In the extreme, one may see designs in which two or more regulators have the same nominal (room temperature) voltage, but different temperature coefficients.

When multiple source voltages are required, generating them by multiple switching converters can require a large number of components. It is often more practical to generate multiple source voltages by employing a single switching converter to generate a relatively high voltage, then using several linear regulators to create the required voltages from the switching converter output. This scheme is especially useful when the unregulated switching converter output voltage itself is used to supply a load, when the currents supplied by the lower voltage supplies are small in comparison to the current used by that load, and when the desired linear regulator output voltage is not too far from that of the switching converter output voltage. It must always be kept in mind that the current supplied by the linear regulators is very expensive in terms of the current drawn from the primary source (e.g., a battery) used to produce it, due to their derivation from the relatively high switching converter output voltage. This system can be much more economical to produce, however, and occupy much less physical area than an alternative design employing multiple switching converters.

Although in principle this concept could be extended, producing lower output voltages by placing linear voltage regulators as the loads of other linear regulators (with higher output voltages), each voltage converter has a power consumption of its own. The efficiency of the system is equal to the multiplication of the efficiencies of each of the converters, which make such "daisy-chaining" of regulators inefficient when more than a very few are used. It is best when the minimum number of voltage conversions is made.

[99]John D. Lenk, Simplified Design of Switching Power Supplies. Boston: Butterworth-Heinemann. 1995.


129 times read

Related news

» Loads
by admin posted on Jul 15,2007
» Mains
by admin posted on Jul 15,2007
» Types of Voltage Converters
by admin posted on Jul 15,2007
» POWER MANAGEMENT STRATEGY
by admin posted on Jul 15,2007
» Things to Look for After the Schematics Are Done but Before the Layouts Are Started
by admin posted on Jul 15,2007


More Top News
Cisco Wireless Networking
Most Popular
Featured Author

Rifat Sanaç

image
wireless master.